Publication 1747-RM001G-EN-P - November 2008
14-8 SLC Passthru Communications
Using RSLinx Classic, version 2.50 and higher, with SLC 5/04
Passthru
RSLinx Classic, version 2.42 and below, only supports DF1 Full-duplex to
DH+, DF1 Half-duplex Master to DH+, DH-485 to DH+, DH+ to DF1
Full-duplex, and DH+ to DH-485 passthru. RSLinx Classic, version 2.43
supports all modes of channel-to-channel passthru described below, except
when channel 0 control line handshaking is enabled. RSLinx Classic, version
2.50 and higher supports all modes of channel-to-channel passthru as
described below.
When channel 0 is configured for DF1 Full-duplex and S:34/5=1, the SLC
5/04 passthru processor can be used by RSLinx to go online through channel
0 to the channel 1 DH+ network. The RSLinx RS-232 DF1 driver is used,
with the device configured for 1770-KF2/1785-KE. The passthru processor
will appear on the RSWho browse at its DH+ node address. You should
configure the properties of the DH+ network within RSWho to only browse
the specific range of addresses that are being utilized on the DH+ network.
When channel 0 is configured for DF1 Half-duplex Master and S:34/5=1, the
SLC 5/04 passthru processor can be used by RSLinx to go online through
channel 0 to the channel 1 DH+ network. The RSLinx DF1 Slave driver is
used. The SLC 5/04 passthru processor channel 0 configuration must be set
up in Standard Polling Mode, and the slave address of RSLinx must be
included in the polling range. The DF1 Slave driver properties in RSWho must
be modified to poll for the valid 5/04 DF1 Half-duplex Master passthru range
of addresses, which is 128 to 191 (for DH+ nodes 0 to 77 octal or 0 to 63
decimal). The passthru processor will appear on the RSWho browse at 128
plus its decimal DH+ node address. You should configure the properties of
the DH+ network within RSWho to only browse the specific range of
addresses that are being utilized on the DH+ network.
When channel 0 is configured for DH-485 and S:34/0=0, the SLC 5/04
passthru processor can be used by RSLinx to go online through channel 0 to
the channel 1 DH+ network, when the PC running RSLinx is directly
connected to the DH-485 network through a 1784-KTX(D), -PKTX(D), or –
PCMK card. When RSWho is browsing the SLC 5/04 on DH-485 with
S:34/0=0, then a ‘+’ sign will appear to the left of the SLC 5/04 icon. Clicking
on the ‘+’ sign will expose a DH+ network underneath the SLC 5/04 icon.
Clicking on the ‘+’ sign to the left of the DH+ network will result in RSWho
browsing for nodes 0 to 77 (octal) on the DH+ network. You should
configure the properties of the DH+ network within RSWho to browse the
specific range of addresses that are being utilized on the DH+ network.
When channel 0 is configured for either DF1 Full-duplex, DF1 Half-Duple
Master, DF1 Radio Modem (with S:34/5=1), or DH-485 (with S:34/0=0), the
SLC 5/04 passthru processor can be used by RSLinx to go online through
channel 1 to the channel 0 DF1 or DH-485 network, as long as the PC
running RSLinx is directly connected to the DH+ network through a

Table of Contents

Other manuals for Allen-Bradley SLC 500 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SLC 500 Series and is the answer not in the manual?

Allen-Bradley SLC 500 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelSLC 500 Series
CategoryController
LanguageEnglish

Related product manuals