16-4 Troubleshooting Faults
Going-to-run Errors
0008 Internal software error. An unexpected software error
occurred due to:
• Either noise,
• lightning,
• improper grounding,
• lack of surge suppression on
output with inductive loads, or
• poor power source.
Correct the problem, reload the
program, and run. You can use the
autoload feature with a memory
module to automatically reload the
program and enter the Run mode.
If the problem re-occurs, contact your
RSI representative.
0009 Internal hardware error. An unexpected hardware error
occurred due to:
• Either noise,
• lightning
• improper grounding,
• lack of surge suppression on
output with inductive loads,
or
• poor power source.
Correct the problem, reload the
program, and run. You can use the
autoload feature with a memory
module to automatically reload the
program and enter the Run mode.
If the problem re-occurs, contact your
local Rockwell Automation
representative.
— With the keyswitch in the RUN
position, the SLC processor powers
up in a non-RUN state.
The keyswitch may be damaged. Connect RS Logix 500 to the SLC
processor. If the processor status
shows "Remote Download in
Progress" and status bits S:1/0-4 are
all cleared, please contact your local
Rockwell Automation representative.
Table 16.1 Powerup Errors
Error Code
(Hex)
Description Probable Cause Recommended Action
Table 16.2 Going-to-Run Errors
Error Code
(Hex)
Description Probable Cause Recommended Action
0010 The processor does not meet the
required revision level.
The revision level of the processor is
not compatible with the revision level
for which the program was
developed.
Consult your your local Rockwell
Automation representative to
purchase an upgrade kit for your
processor.
0011 The executable program file number 2
is absent.
Incompatible or corrupt program is
present.
Reload the program or reprogram
with RSI programming software.