D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
Bosch | 7/05 | 31499J 37
7.1.3 Daylight Savings
Shortcut:
0-PROG > 1-PROG TIME > 3-DAYLIGHT SAV
This feature enables automatic adjustment of system
time for Daylight Savings. The dates for the adjustment
are pre-programmed in the system. The following
window appears:
1. Press [1] to DISABLE or [2] to ENABLE.
2. After programming, the preceding window appears.
7.2 Security
7. 2 .1 P I N s
Programmer PIN
Shortcut:
0-PROG > 2-SECURITY > 1-PINS
The Programmer PIN is the code the installer uses to
configure and operate the control panel. The factory
default code is 9876 and can be changed at any time.
The following window appears:
1. Press [1] for PROGRAMR PIN and access:
2. Enter the PIN and press [#].
3. After programming the programmer PIN, the
preceding window appears.
Program User PINs
Shortcut:
0-PROG > 2-SECURITY > 1-PINS
Up to 15 additional user codes, or up to 99 additional
users when the D7039 is installed, can be programmed
for the unit to protect the system from unauthorized
operation. Also, a record of individual system user
actions is kept. The following window appears:
1. Press [2] for USER PINS and access:
2. Enter the user for whom you want to program a
PIN and press [#]. For example, for User 5, press
[5]. The following window appears:
3. Enter the PIN and press [#].
4. After programming the User PIN, the preceding
window appears.
7.2.2 Authority
Shortcut:
0-PROG > 2-SECURITY > 2-AUTHORITY
This feature determines which system actions a user can
perform. Refer to Ta b l e 19 for PIN authority levels.
1- DISABLE
2- ENABLE
DAYLIGHT SAV
1- PINS
2- AUTHORITY
SECURITY
1- PROGRAMR PIN
2- USER PINS
PROGRAM PINS
USER 0
ENTER PIN: _____
Table 19: PIN Authority Levels
PIN Authority Level Allowed Operations
Maximum (1) All control panel operations, includ-
ing programming.
Medium (2) System test modes, fire drill, reset,
disable, silence, view history.
Minimum (3) Silence, view history.
None (0) None.
PROGRAM PINS
1- PROGRAMR PIN
2- USER PINS
OTHER PINS
USER (01-15)
USER 5
ENTER PIN: _____

Table of Contents

Other manuals for Bosch D7024

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch D7024 and is the answer not in the manual?

Bosch D7024 Specifications

General IconGeneral
BrandBosch
ModelD7024
CategoryControl Panel
LanguageEnglish

Related product manuals