D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
38 Bosch | 7/05 | 31499J
The following window appears:
1. Enter the user for whom you want to program
authority and press [#]. The following window
appears and scrolls its options:
2. Press the number key corresponding to your
selection. The current setting appears in parentheses
on the first line.
3. After programming, the preceding window appears.
7.3 PROG System
7.3.1 Program Timers
Shortcut:
0-PROG > 3-PROG SYSTEM > 2-TI ME RS
The following window appears:
Smoke Reset
Shortcut:
0-PROG > 3-PROG SYSTEM > 2-TI ME RS
This feature designates the length of time the smoke
detector power is turned off after reset. The system does
not register alarms for 5 sec after power on.
The display scrolls through the TIMERS options.
1. Press [1] for SMOKE RESET to access:
2. Enter the value and press [#]. The current setting
appears in parentheses on the first line.
3. After programming, the preceding window appears.
AC Fail Delay
Shortcut:
0-PROG > 3-PROG SYSTEM > 2-TIM ERS
This feature sets the number of hours the control panel
waits after an AC failure and before sending an AC
Failure Report. A setting of “DC” causes the system to
send a report when 25% of the battery capacity is used.
The display scrolls through the TIMERS options.
1. Press [2] for AC FAIL DELAY to access:
2. The wait for DC function causes the AC Fail Report
to be sent when the battery is 25% depleted, based
on the measured voltage of the battery. If you want
to WAIT FOR DC (25 percent of capacity), press
[1].
The current setting appears in parentheses on the
first line, either “DC”, or the number of hours
selected.
3. After programming the AC Fail Delay, the
preceding screen appears. If you want to ENTER
TIME, press [2] to access:
4. Enter the time and press [#].
The current setting appears in parentheses on the
first line.
5. After programming the AC Fail Delay, the
preceding window appears.
When WAIT FOR DC is the current selection, the
Enter Time Menu shows DC as the time in hours.
AUTHORITY
USER (01-15)
0- NONE
1- MAXIMUM
2- MEDIUM
3- MINIMUM
USER 1 ATHRY ( )
PROG SYSTEM
1- (reserved)
2- TIMERS
3- AC LINE SYNC
4- OPTION BUS
5- PIN REQUIRED?
6- (reserved)
7- REMOTE PGM
1- SMOKE RESET
2- AC FAIL DLY
3- AUTO SILENCE
4- (reserved)
5- DISPLAY RATE
TIMERS
SMOKE RESET (_ _)
(1-16 SEDS): _ _
1- WAIT FOR DC
2- ENTER TIME
AC FAIL DELAY
AC FAIL DLY (_ _ _)
(01-24 HRS):_ _ _ _

Table of Contents

Other manuals for Bosch D7024

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch D7024 and is the answer not in the manual?

Bosch D7024 Specifications

General IconGeneral
BrandBosch
ModelD7024
CategoryControl Panel
LanguageEnglish

Related product manuals