N O T I C E
For salient PM motors: AMA is not available. If only line-line data is available, divide the line-line value by 2 to achieve the line-to-
common (star point) value. Alternatively, measure the value with an ohmmeter. This also takes the resistance of the cable into
account. Divide the measured value by 2 and enter the result.
N O T I C E
The parameter value is updated after each torque calibration if option [3] 1st start with store or option [4] Every start with store is
selected in parameter 1-47 Torque Calibration.
Parameter 1-31 Rotor Resistance (Rr)
Table 85: Parameter 1-31 Rotor Resistance (Rr)
1-31 Rotor Resistance (Rr)
Default value: Size related
Parameter type: Range, 0.0100 - 100.0000 Ohm
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: False
N O T I C E
Parameter 1-31 Rotor Resistance (Rr) has no effect when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM, [5]
SynRM.
Set the rotor resistance value R
r
to improve shaft performance using 1 of these methods:
Run an AMA on a cold motor. The drive measures the value from the motor. All compensations are reset to 100%.
Enter the R
r
value manually. Obtain the value from the motor supplier.
Use the R
r
default setting. The drive establishes the setting based on the motor nameplate data.
Parameter 1-33 Stator Leakage Reactance (X1)
Table 86: Parameter 1-33 Stator Leakage Reactance (X1)
1-33 Stator Leakage Reactance (X1)
Default value: Size related
Parameter type: Range, 0.0400 - 400.0000 Ohm
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: False
N O T I C E
This parameter is only relevant for asynchronous motors.
Set the stator leakage reactance of the motor using 1 of these methods:
Run an AMA on a cold motor. The drive measures the value from the motor.
Enter the X
1
value manually. Obtain the value from the motor supplier.
Use the X
1
default setting. The drive establishes the setting based on the motor nameplate data.
N O T I C E
The parameter value is updated after each torque calibration if option [3] 1st start with store or option [4] Every start with store is
selected in parameter 1-47 Torque Calibration.
AU275636650261en-000101 / 130R033482 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals