Parameter 1-34 Rotor Leakage Reactance (X2)
Table 87: Parameter 1-34 Rotor Leakage Reactance (X2)
1-34 Rotor Leakage Reactance (X2)
Default value: Size related
Parameter type: Range, 0.0400 - 400.0000 Ohm
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: False
N O T I C E
This parameter is only relevant for asynchronous motors.
Set the rotor leakage reactance of the motor using 1 of these methods:
Run an AMA on a cold motor. The drive measures the value from the motor.
Enter the X
2
value manually. Obtain the value from the motor supplier.
Use the X
2
default setting. The drive establishes the setting based on the motor nameplate data.
N O T I C E
The parameter value is updated after each torque calibration if option [3] 1st start with store or option [4] Every start with store is
selected in parameter 1-47 Torque Calibration.
Parameter 1-35 Main Reactance (Xh)
Table 88: Parameter 1-35 Main Reactance (Xh)
1-35 Main Reactance (Xh)
Default value: Size related
Parameter type: Range, 1.0000 - 10000.0000 Ohm]
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
Parameter 1-35 Main Reactance (Xh) does not have effect when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM.
Set the main reactance of the motor using 1 of these methods:
Run an AMA on a cold motor. The drive measures the value from the motor.
Enter the X
h
value manually. Obtain the value from the motor supplier.
Use the X
h
default setting. The drive establishes the setting based on the motor nameplate data.
N O T I C E
The parameter value is updated after each torque calibration if option [3] 1st start with store or option [4] Every start with store is
selected in parameter 1-47 Torque Calibration.
AU275636650261en-000101 / 130R0334 | 83Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals