14-62 Inv. Overload Derate Current
Range: Function:
95 %* [50 -
100 %]
Denes the desired current level (in % of
rated output current for the frequency
converter) when running with reduced pump
speed after load on the frequency converter
has exceeded the allowable limit (110% for
60 s).
14-90 Fault Level
Option: Function:
[0] O Use this parameter to customize Fault levels. Use
[0] O with caution as it will ignore all Warnings &
Alarms for the chosen source.
[1] Warning
[2] Trip
[3] Trip Lock
Failure Alarm O War-
ning
Trip Trip
Lock
Over Current 13 D X
Motor phase
missing
30 D X
Motor phase
missing
31 D X
Motor phase
missing
32 D X
Table 6.10 Table for Selection of Choice of Action when Selected
Alarm Appears
D = Default setting. x = possible selection.
1) Only high power drives
In FC small and medium A69 is only a warning