14-62 Inv. Overload Derate Current
Range: Function:
95 %* [50 -
100 %]
Denes the desired current level (in % of
rated output current for the frequency
converter) when running with reduced pump
speed after load on the frequency converter
has exceeded the allowable limit (110% for
60 s).
14-90 Fault Level
Option: Function:
[0] O Use this parameter to customize Fault levels. Use
[0] O with caution as it will ignore all Warnings &
Alarms for the chosen source.
[1] Warning
[2] Trip
[3] Trip Lock
Failure Alarm O War-
ning
Trip Trip
Lock
Over Current 13 D X
Motor phase
missing
30 D X
Motor phase
missing
31 D X
Motor phase
missing
32 D X
Table 6.10 Table for Selection of Choice of Action when Selected
Alarm Appears
D = Default setting. x = possible selection.
1) Only high power drives
In FC small and medium A69 is only a warning
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
104 Danfoss A/S © Rev. 2013-07-03 All rights reserved. MG34M422
6
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 303 and is the answer not in the manual?

Danfoss VLT CDS 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 303
CategoryDC Drives
LanguageEnglish

Related product manuals