13-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Smart
Logic Control.
Option: Function:
[80] Digital input x46/3
[81] Digital input x46/5
[82] Digital input x46/7
[83] Digital input x46/9
[84] Digital input x46/11
[85] Digital input x46/13
[90] ATEX ETR cur. warning Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the alarm 164 ATEX ETR
cur.lim.alarm is active, the output
will be 1.
[91] ATEX ETR cur. alarm Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output
will be 1.
[92] ATEX ETR freq. warning Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the
output will be 1.
[93] ATEX ETR freq. alarm Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94] RS Flipop 0 See parameter group 13-1*
Comparators
[95] RS Flipop 1 See parameter group 13-1*
Comparators
[96] RS Flipop 2 See parameter group 13-1*
Comparators
[97] RS Flipop 3 See parameter group 13-1*
Comparators
[98] RS Flipop 4 See parameter group 13-1*
Comparators
[99] RS Flipop 5 See parameter group 13-1*
Comparators
[100] RS Flipop 6 See parameter group 13-1*
Comparators
13-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Smart
Logic Control.
Option: Function:
[101] RS Flipop 7 See parameter group 13-1*
Comparators
13-03 Reset SLC
Option: Function:
[0] Do not reset
SLC
Retains programmed settings in all parameter
group 13-** Smart Logic Control.
[1] Reset SLC Resets all parameters in parameter group 13-
** Smart Logic Control to default settings.
6.10.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
xed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Figure 6.15 Comparators
In addition, there are digital values that will be compared
to xed time values. See explanation in
parameter 13-10 Comparator Operand. Comparators are
evaluated once in each scan interval. Use the result (TRUE
or FALSE) directly. All parameters in this parameter group
are array parameters with index 0 to 5. Select index 0 to
programme Comparator 0, select index 1 to programme
Comparator 1, and so on.
13-10 Comparator Operand
Array [6]
Option: Function:
Choices [1] to [31] are variables which will
be compared based on their values.
Choices [50] to [186] are digital values
(TRUE/FALSE) where the comparison is
based on the amount of time during
which they are set to TRUE or FALSE,
respectively. See
parameter 13-11 Comparator Operator.
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
88 Danfoss A/S © Rev. 2013-07-03 All rights reserved. MG34M422
6