13-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Smart
Logic Control.
Option: Function:
[80] Digital input x46/3
[81] Digital input x46/5
[82] Digital input x46/7
[83] Digital input x46/9
[84] Digital input x46/11
[85] Digital input x46/13
[90] ATEX ETR cur. warning Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the alarm 164 ATEX ETR
cur.lim.alarm is active, the output
will be 1.
[91] ATEX ETR cur. alarm Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output
will be 1.
[92] ATEX ETR freq. warning Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the
output will be 1.
[93] ATEX ETR freq. alarm Selectable if parameter 1-90 Motor
Thermal Protection is set to [20]
ATEX ETR or [21] Advanced ETR. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94] RS Flipop 0 See parameter group 13-1*
Comparators
[95] RS Flipop 1 See parameter group 13-1*
Comparators
[96] RS Flipop 2 See parameter group 13-1*
Comparators
[97] RS Flipop 3 See parameter group 13-1*
Comparators
[98] RS Flipop 4 See parameter group 13-1*
Comparators
[99] RS Flipop 5 See parameter group 13-1*
Comparators
[100] RS Flipop 6 See parameter group 13-1*
Comparators
13-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Smart
Logic Control.
Option: Function:
[101] RS Flipop 7 See parameter group 13-1*
Comparators
13-03 Reset SLC
Option: Function:
[0] Do not reset
SLC
Retains programmed settings in all parameter
group 13-** Smart Logic Control.
[1] Reset SLC Resets all parameters in parameter group 13-
** Smart Logic Control to default settings.
6.10.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
xed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Figure 6.15 Comparators
In addition, there are digital values that will be compared
to xed time values. See explanation in
parameter 13-10 Comparator Operand. Comparators are
evaluated once in each scan interval. Use the result (TRUE
or FALSE) directly. All parameters in this parameter group
are array parameters with index 0 to 5. Select index 0 to
programme Comparator 0, select index 1 to programme
Comparator 1, and so on.
13-10 Comparator Operand
Array [6]
Option: Function:
Choices [1] to [31] are variables which will
be compared based on their values.
Choices [50] to [186] are digital values
(TRUE/FALSE) where the comparison is
based on the amount of time during
which they are set to TRUE or FALSE,
respectively. See
parameter 13-11 Comparator Operator.
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
88 Danfoss A/S © Rev. 2013-07-03 All rights reserved. MG34M422
6
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 303 and is the answer not in the manual?

Danfoss VLT CDS 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 303
CategoryDC Drives
LanguageEnglish

Related product manuals