6.14 Par. Group 25 - Cascade Controller
Parameters for conguring the Basic Cascade Controller for
sequence control of multiple compressors.
Figure 6.24 Cascade Controller Feedback Signals
To congure the Cascade Controller to the actual system
and the desired control strategy, it is recommended to
follow the below sequence, starting with parameter group
25-0* System Settings, and next parameter group 25-5*
Alternation Settings.These parameters can normally be set
in advance.
Parameters in parameter group 25-2* Bandwidth Settings
and 25-4* Staging settings will often be dependent on the
dynamic of the system and nal adjustment to be done at
the commissioning of the plant.
NOTICE!
The Cascade Controller is supposed to operate in closed
loop controlled by the built-in PI controller ([1] Speed
Closed Loop selected in parameter 1-00 Conguration
Mode). If [0] Speed Open Loop is selected in
parameter 1-00 Conguration Mode, all xed speed
compressors will be destaged, but the variable speed
compressor will still be controlled by the frequency
converter, now as an open loop conguration:
Figure 6.25 Conguring the Cascade Controller
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
112 Danfoss A/S © Rev. 2013-07-03 All rights reserved. MG34M422