6.2 Par. Group 0 - Operation and Display
6.2.1 0-0* Basic Settings
0-01 Language
Option: Function:
[0] English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
[10] Chinese
[28] Bras.port
[39] Korean
[42] Trad.Chinese
[49] Russian
0-02 Motor Speed Unit
Option: Function:
Select display of motor speed parameters (i.e.
references, feedbacks and limits) in terms of shaft
speed (RPM) or output frequency to the motor (Hz).
[0] RPM
[1] Hz
NOTICE!
This parameter cannot be adjusted while the motor is
running.
0-04 Operating State at Power-up (Hand)
Option: Function:
Selects the operating mode upon reconnection
of the frequency converter to mains voltage
after power down in Hand (local) operation
mode.
[0] Resume Restarts the frequency converter, maintaining
the same and the same start/stop settings
(applied by [Hand On/O]) as before the
frequency converter was powered down.
[1] Forced stop,
ref=old
Restarts the frequency converter with a saved
local reference, after mains voltage reappears
and after pressing [Hand On].
[2] Forced stop,
ref=0
Resets the local reference to 0 upon restarting
the frequency converter.
0-10 Active Set-up
Option: Function:
Select the set-up to control the frequency
converter functions.
0-10 Active Set-up
Option: Function:
[0] Factory
setup
Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a known
state.
[1] Set-up 1 [1] Set-up 1 to [4] Set-up 4 are the four separate
parameter set-ups within which all parameters
can be programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-
up
Remote selection of set-ups using digital inputs
and the serial communication port. This set-up
uses the settings from parameter 0-12 This Set-
up Linked to. Stop the frequency converter
before making changes to open- and closed
loop functions
Use parameter 0-51 Set-up Copy to copy a set-up to one or
all other set-ups. Stop the frequency converter before
switching between set-ups where parameters marked ‘not
changeable during operation’ have dierent values. To
avoid conicting settings of the same parameter within
two dierent set-ups, link the set-ups together using
parameter 0-12 This Set-up Linked to. Parameters which are
‘not changeable during operation’ are marked FALSE in the
parameter lists in chapter 6.16 Parameter Lists.
0-11 Edit Set-up
Option: Function:
Select the set-up to be edited (i.e.
programmed) during operation; either the
active set-up or one of the inactive set-ups.
[0] Factory
setup
Cannot be edited but it is useful as a data
source to return the other set-ups to a known
state.
[1] Set-up 1 [1] Set-up 1 to [4] Set-up 4 can be edited freely
during operation, independently of the active
set-up.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Active Set-
up
Can also be edited during operation. Edit the
chosen set-up from a range of sources: LCP, FC
RS-485, FC USB or up to ve eldbus sites.
Parameter Descriptions Operating Instructions
MG34M422 Danfoss A/S © Rev. 2013-07-03 All rights reserved. 47
6
6