AO Function Block
March 2006
5-71
PV_SCALE Set the range and engineering units
to values that correspond to the op-
eration range. For the digital valve
controller, PV_SCALE [11] is
typically set between 0 and 100%.
BKCAL_OUT If you are using the CAS_IN [17]
connector wired from another block,
wire the BKCAL_OUT [25] attribute
to the other block’s BKCAL_IN [27]
attribute.
IO_OPTS Set the type of tracking and action
upon fault state.
SHED_OPT Set the action to be taken when the
set point or output are not updated
in a remote mode.
Block Errors
Table 5-23 lists conditions reported in the
BLOCK_ERR [6] parameter. Conditions in italics are
not applicable for the AO block and are provided only
for your reference.
Table 5-23. BLOCK_ERR Conditions
Condition
Number
Condition Name and Description
0 Other (N/A)
1
Block Configuration Error - CHANNEL and SHED_OPT
set to 0
2 Link Configuration Error (N/A)
3
Simulate active - Simulation is enabled and the block is
using a simulated value in its execution.
4 Local Override - Device in fault state. Actual mode LO.
5
Device Fault State Set - AO block in fault state after
FSTATE_TIME because of Bad status or IFS substatus
on CAS_IN or Resource block commanded fault state.
6
Device Needs Maintenance Soon - Indicates a
Maintenance PlantWeb Alert condition is active if Block
Error Reporting is enabled. See page 5-39.
7
Input failure/process variable has Bad status - PV has
bad status and Feature Select in the Resource block has
the Out Readback bit set.
8 Output failure - PV has bad status.
9 Memory Failure (N/A)
10 Lost Static Data (N/A)
11 Lost NV Data (N/A)
12 Readback Check Failed (N/A)
13
Device Needs Maintenance Now - Indicates Failed
PlantWeb Alert condition is active if Block Error Reporting
is enabled. See page 5-39.
14
Power Up - This condition exists after power up until
actual mode is not Out of Service.
15
Out of Service - The block is in Out of Service (OOS)
mode.
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6020f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6020f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6020f
CategoryController
LanguageEnglish

Related product manuals