CHAPTER 4: SETPOINTS DEVICE
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–17
SNTP FUNCTION
Range: Disabled, Enabled
Default: Disabled
SNTP SERVER IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
SNTP SERVER 2 IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP 2 UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
FAST PATH:
The SNTP and PTP settings take effect after rebooting the relay.
Security
The following security features are available:
Basic Security – The basic security feature present in the default offering of the
product.
CyberSentry – The feature refers to the advanced security options available as a
software option. When this option is purchased, it is automatically enabled and Basic
Security is disabled.
GENERAL RULES FOR ROLES
All the roles are password protected, except for the Observer role which is user
defined on the device. A user with Observer capability defined on the Radius is
password protected.
All the roles, except for the Observer role, support only one session at one time.
The Observer role has read-only access to all values in the relay except for one service
command which is described in the Password Recovery Procedure section.
All the roles, except for the Observer, have access to a “log out” setting, which has the
effect of switching to Observer role.
A Setpoint access setting for bypassing security is available. If this feature is used, the
user gains total access for any operations / configuration changes executed either
from the front panel or from EnerVista.
The setpoint access setting may be either switched directly on or assigned to a digital
input.
If the setpoint access setting is assigned to a digital input, the digital input needs to be
activated through a physical key (jumper).
The setpoint access setting may be set only by an Administrator.
PASSWORD COMPLEXITY
The password complexity is available on both Basic Security and CyberSentry.
If password complexity is enabled, a user account requires an alpha-numeric password
that meets the following requirements:
Passwords cannot contain the user account name or parts of the user's full name that
exceed two consecutive characters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 845 and is the answer not in the manual?

GE 845 Specifications

General IconGeneral
BrandGE
Model845
CategoryProtection Device
LanguageEnglish

Related product manuals