*1. The "02" setting may not be available according to the type of indoor unit.
*2. 00:Standard of Indoor Unit 01:100 hours 02:1200 hours 03:2500 hours 04:No Indication
*3. In case of RPI models, 00: Increasing fan speed 1 (standard), 01: Increasing fan speed 2 (high static pressure), 02: Standard (low static pressure)
*4. 01: Control by Thermistor of Remote Control Switch 02: Control by Average Value of Indoor Suction Thermistor and Thermistor of Remote Control Switch
Sheet A Optional Setting Items
b1
b2
b3
b4
b5
b6
b7
b8
b9
C1
C2
C3
C4
C5
C6
C7
C8
C9
CA
CB
CC
Removal of Heating
due to Uneven Heat Load
Circulator Function at
Enforced 3 Minutes Minimum
Operation Time of Compressor
Change of Filter Cleaning Time
Fixing of Operation Mode
Fixing of Setting Temperature
Exclusive Cooling Unit
Automatic COOL/HEAT
Operation
Fixing of Fan Speed
Not Prepared
Not Prepared
Not Prepared
Not Prepared
Hi Speed
Hi Speed at Heating
Thermo-OFF
Canceling of Enforced 3
3 Minutes Minimum Operation
Time of Compressor
Thermistor of Remote Control
Switch
Not Prepared
Not Prepared
Selection of Forced Stoppage
Not Prepared
00:Standard 01:Removal
02:Set Temp.+2°C(*1)
00:Not Available
00-04(*2)
00:Not Available 01:Available
00:Not Available 01:Available
00:Not Available 01:Available
Not Used
Not Used
00:Not Available
02: Hi Speed 2(*3)
00:Not Available 01,02(*4)
Not Used
Not Used
00:A Contact 01:B Contact
Use as 00 conditions
Setting
item
Setting
item
Name
Individual
setting
Setting content setting Name
Individual
setting
Setting content setting
00:Not Available 01:Available
Not Used
00:Not Attached 01:Attached
00:Standard 01:30minutes
02:60minutes
00-24 : OFF Timer by
00 : Main
01 : Sub
d1
d2
d3
E1
E2
E3
E4
E5
F1
F2
The power supply start stop 1
Not Prepared
Power Supply ON/OFF 2
Ventilation Model
Increasing Supply Air Volume
With a humidifier
Time of Precooling and
preheating
Automatic OFF Timer Setting
Remote Control Main-Sub
Setting
Logic
NOTES:
* After at least 3 minutes from the power ON, change the optional setting.
* The optoinal settings are different according to the indoor and outdoor unit models. Check to ensure that the unit has the optional
setting or not.
* Record the setting conditions for each optional setting in the "Setting" column of the table.
●
T
able B Input and Output Number Display and Connectors
●
Table C Input and Output Settings and Display Codes
Input number
display
Port Factory Setting Setting
Input / Output Indication Setting Item Indiicaton
Input1 CN3 1-2 Remote ON/OFF 1 (level) 03
Input2 CN3 2-3 F
orbidding Remote Control
after Manual Stoppage
06
Output1 CN7 1-2 Operation 01
Output2 CN7 1-3 Alarm 02
Output3 CN8 1-2 Thermo-ON for Heating 06
Indication Input Output
00 Not set Not set
01 Room
Thermostat (for Cooling)
Operation
02
Room Thermostat (for Heating) Alarm
03 Remote ON/OFF 1 (level) Cooling
04 Remote ON/OFF 2 (Operation) Thermo-ON for
Cooling
05 Remote ON/OFF 2 (Stoppage) Heating
06 Forbidding Remote Control
after Manual Stoppage
Thermo-ON for
Heating
07 Remote Cooling / Heating
Change
Total Heat Exchanger
08 Elevating grille input Elevating Grille output
NOTES:
* After at least 3 minutes from the power ON, change the optional setting.
* The elevating grille input can be set to Input 2 only " " .
The elevating grille cannot be set to Input 1.
* The elevating grille output can be set to Output 1 or Output 2 only " " or " " .
The elevating grille output cannot be set to Output 3.
* Do not set the elevating grille for the total heat exchanger
.
* Record the setting conditions for each input and output in the "Setting" column of the table.
Not Prepared
Temperature Compensation
Heating Thermo-OFF
01
:
Available
00:Not Available
01
:
Available
Fixing of Operation as
00:Not Available 01:Available
00:Not Available 01:Available
Not Used
Not Used
01: Hi Speed 1(*3)
00:Not Available 01:Available
00:Available 01:Not Available
00:Not Available 01:Available
00:Not Available 01:Available
Not Used
0-24hours