Enhanced Micro TDC 3000 User’s Manual 2-1 9/95
2
SITE PREPARATION AND INSTALLATION
Section 2
This section provides the following information for the Enhanced Micro TDC 3000
Control
System: Storage conditions, site requirements, electrical requirements, unpacking, cabling, and
node addressing.
2.1 STORAGE CONDITIONS
The Enhanced Micro TDC 3000 Control System is protectively wrapped for shipment in a
dry-wall pack. The electronics modules, color monitor, operator’s keyboard, engineer’s
keyboard, touchscreen, trackball, and printer are in separate packages.
If the Enhanced Micro TDC 3000 Control System is to be placed in storage, the
environmental constraints listed here must be followed:
Temperature -10° + 70°C
Humidity (RH) 10 - 80%, max wet bulb 20 - 30°C
Shock* 3.0 g for 10 milliseconds
* When enclosed in the original shipping container.
Note that the temperature/relative humidity shall not be cycled such that moisture
condensation occurs on the equipment—rate of change less than 6% per hour. The storage
shipping requirements are for one year duration only, provided the equipment is properly
packaged and contains an adequate amount of desiccant (moisture removing agent).
2.2 SITE REQUIREMENTS
The Enhanced Micro TDC 3000 Control System is designed for a Class C (office)
environment. It must be operated in a temperature environment of 0°-45°C (32°-113°F).
While operating, components of this system are not designed to withstand greater vibration
than:
5-22 Hz 0.254 mm (0.010 inch) displacement
22-500 Hz 0.25 g
For US systems, each electronics module, the monitor(s), and the printer are equipped with
1.8 meter (6 foot) NEMA 5-15P, power cords. For the basic Enhanced Micro TDC 3000
System (refer to subsection 1.1.1), there must be at least two duplex, 120 Vac, grounded,
NEMA 5-15R, electrical outlets accessible to these items. These outlets must be tied to the
same ground.
If your system is equipped with additional color monitors, there must be at least three
duplex, 110 Vac, grounded, NEMA 5-15R, electrical outlets, all tied to the same ground.
Additional outlets are also needed if certain options are installed—for example, the EPLCG
option may use a free-standing modem powered from 110 Vac lines.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Enhanced Micro TDC 3000 and is the answer not in the manual?

Honeywell Enhanced Micro TDC 3000 Specifications

General IconGeneral
BrandHoneywell
ModelEnhanced Micro TDC 3000
CategoryController
LanguageEnglish

Related product manuals