Enhanced Micro TDC 3000 User’s Manual 5-6 9/95
5.1.1
5.1.1.5 How to Set the Time and Date
1. Press the SYSTEM STATUS display key on the Operator’s Console. On the System
Status display, select the TIME/DATE target.
2. A port opens with a prompt to enter the time. Key in the time in hours and minutes (for
example, 14 25).
3. Press ENTER and the current time should appear in the upper right corner.
4. A port opens with a prompt to enter the date. Key in the current day, month and year
(for example, 15 OCT 91).
5. Press ENTER and the current date should appear in the upper right corner.
5.2 LOADING THE MODULES AND GATEWAYS
At this point, at least one US should be running the Operating Personality. If you went
through the implementation procedures in Section 4 of this manual, the modules should
already be loaded and running. If you didn’t go through the steps in Section 4 (or if you
just want to check the modules), press the SYST STATUS key on the Operator’s
Keyboard. Select the HISTORY MODULES target. If it doesn’t have a status of OK you
should not continue until the problem is fixed.
Return to the System Status Display either by pressing the PRIOR DISP key or the SYST
STATUS key. One by one, select the other module and gateways targets on the System
Status display and check each implemented module for a status of OK (OK indicates the
Operating Personality is running in the module). An unimplemented module has a status of
OFF. An implemented but unloaded module usually has a status of PWR ON.
If any implemented module does not have a status of OK, use the following procedures to
load the module. Refer to 5.1.1.3 to load another Universal Station.
If the system has an optional CG or PLCG, refer to Section 18 in the System Startup
Guide—Cartridge Drive for the module loading procedures.
5.2.1 Loading the Application Module
The Application Module is loaded through the Application Modules Status display, which
is called up by selecting APPLICATION MODULES on the System Status display.
1. Select the node number 5 (the AM).
2. If the AUTOLOAD NET target is present, select AUTOLOAD NET, press ENTER,
and skip to step 4. Otherwise, select MANUAL LOAD. Continue with step 3.
3. Select OPERATOR PROGRAM, and follow the prompters to specify the program and
data source [normally, you will select the default source (NET = HM)]. Then,
select EXECUTE COMMAND.
4. Wait from a few seconds to a few minutes for the status for the AM to go to OK.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Enhanced Micro TDC 3000 and is the answer not in the manual?

Honeywell Enhanced Micro TDC 3000 Specifications

General IconGeneral
BrandHoneywell
ModelEnhanced Micro TDC 3000
CategoryController
LanguageEnglish

Related product manuals