Enhanced Micro TDC 3000 User’s Manual 4-15 9/95
4.4.2
9. On the UCN Status display, the target 03 APM should still be selected (filled with
color).
10. Select LOAD/SAVE RESTORE. The box should change to white.
11. Select RESTORE DATA; then select ENTER.
12. On the Restore UCN Node display, select DEFAULT SOURCE, then select
EXECUTE. When RESTORED is displayed, proceed to Step 12.
13. Select DETAIL STATUS. Check the boxes on the Detail Status display. For each
implemented IOP, a box should contain the IOP type (e.g., HLAI) and the word
IDLE.
4.4.2 Expanded Standard APM Cabinet
If you are configuring a double-sided nonredundant cabinet with added IOP cards, use the
procedure in 4.4.1, then reconstitute the entity $NM01B03 (refer to the Data Entity Builder
Manual for the reconstitute procedure). Add the extra I/O Modules to the configuration for
the cabinet. Load the data by pressing F12.
To configure any other APM cabinet, follow the procedures in Task 32 of the System
Startup Guide—Cartridge Drive.
4.4.3 UCN/APM Box Point Configuration Data
The following entity defines the primary Advanced Process Manager Module as node 03 on
process network 01 (the UCN). This checkpoint information was loaded as the Data
Source for the APM. A redundant APM is configured as node 04 but otherwise contains
default values.
Parameter Description Value, Primary APM
(Name) Entity name $NM01N03
NTWKNUM Network number 01
NODENUM Node number 03
NODETYP Node type APM
NODASSN Node assignment ThisNIM
MOVPVTXT Moving text descriptor Neither
BADPVTXT Bad PV text Both
The following entity defines the physical configuration of the Advanced Process Manager
and several key operational characteristics.
Parameter Description Value Parameter Description Value
(Name) Entity name $NM01B03 NPMSLOT No. of Process Module Slots 30
NTWKNUM Network number 01 NUMERIC No. Numerics in PM Box Pnt. 2047
NODENUM Node number 03 SCANRATE Scan rate Reg1Log1
CTLOPT Control option On PKGOPT PMM Packaging Option Nonredun
NCTLSLOT Number of control slots 40 IOMFILEA IOP file number (see chart)
NPVSLOT Number of PV slots 20 IOMCARDA IOP card number (see chart)
NLOGSLOT Nmbr. of Logic slots 25 IOMTYPE IOP card type (see chart)
NDCSLOT Nmbr. of Digital Comp. slots 150 FAILOPT(n) Output failure option Unpower