EXCEL CARE CONTROL ICONS INTRODUCTION
15 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Calculates the derivative output signal, which
changes in proportion to changes of the input
signal. Y = 0 if the input is unchanged since
the last cycle. Y > 0 if the deviation is
increasing. Y < 0 if the deviation is
decreasing.
Divides input A by input B.
Switches HVAC systems alternating on and
Legacy RACL function: Decide on the most
economical system operation for full and
partial air conditioning systems.
Decide on the most economical system
operation for full and partial air conditioning
systems.
Calculate enthalpy (Ent) and absolute
humidity (HAbs) as a function of air
temperature, relative air humidity, and air
pressure. Use Enthalpy with the Economy
function.
Calculate optimized values for starting and
stopping the heating plant and for the supply
water setpoint.
Calculate optimized values for starting and
stopping the heating plant and for the supply
water setpoint.
Calculate optimized values for starting and
stopping air conditioning systems. Systems
should start at the latest possible time and
should stop as soon as possible to save
energy.
Legacy RACL function: Compares "Comp"
input with all other inputs. If at least one input
is equal to the "Comp" input, the output is set
to TRUE (1).
Calculates the exponential.
Calculates the factorial (5! = 1*2*3*4*5).
Legacy RACL function: Calculates an output
according to a user-defined heating
compensation curve.
Calculates an output according to a user-
defined and adaptable heating compensation
curve.
On/off controller that generates a digital
output depending on the deviation of the
controlled variable from the reference
variable. Y1 = 1 if X >= W, Y1 = 0 if X < W –
Hysteresis. Y2 = 1 if X <= W, Y2 = 0 if X > W
+ Hysteresis.