EasyManuals Logo
Home>Honeywell>Control Panel>Galaxy Flex

Honeywell Galaxy Flex Installer Manual

Honeywell Galaxy Flex
246 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Wire detectors to zones Galaxy Flex Installer Manual
18
Figure 4 Option 12 - Double balanced 1k fault/mask monitoring wiring
When this wiring mode is used, ensure only one detector is set to report fault conditions, and
limit the number of detectors or contacts of any type to a maximum of 2.
Note: The recommended maximum cable run from a zone to a detector is 500 metres in all
other configurations.
In end-of-line mode use the wiring shown in Figure 5.
Figure 5 Option 10 - End of Line Zone/Detector wiring
Multiple detector wiring
Multiple detectors can be wired into a single zone when using preset 1 as shown in Figure 6.
The maximum number of detectors that can be connected to a single zone is ten.
Figure 6 Zone to multiple detector wiring
Wire keyswitches
Latching or spring loaded keyswitches can be used to set and unset the panel. To program
keyswitches, refer to Program Zones [52].
If the keyswitch latches, the transition from 1 k to 2 k initiates the setting procedure of
an unset system, the transition from 2 k to 1 k instantly unsets a set system. If the system
is already set, then the transition from 1 k to 2 k has no effect. If the system is unset, the
transition from 2 k to 1 k has no effect. This is programmed as a
Keyswitch in the
Program Zones [52] option.

Table of Contents

Other manuals for Honeywell Galaxy Flex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Flex and is the answer not in the manual?

Honeywell Galaxy Flex Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy Flex
CategoryControl Panel
LanguageEnglish

Related product manuals