Fire Alarm Control Panel IQ8Control C/M
FB 798951.GB0 / 01.09 91
7.1 Technical Data Master box activation module (Part No. 784385)
Operating voltage : Internal via the power supply module, + 5 V DC / +12 V DC
Quiescent current consumption : approx. 10 mA @ 12 V DC (without monitoring)
approx. 15 mA @ 12 V DC (monitored)
Emergency operation : yes
Fuses : Multifuse 1 A
Relay K1 : 1 monitored change-over contact (e.g. MFAB activation)
contact rating max. 30 V DC / 1 A
Monitored resistance 50 to 1000 Ω
Activation time (relay K1) Continuously or pulsed (0,25 s / 1,5 s / 2,5 s or 6 s)
Output "MFAB reset“ : max. 300 mA (+12 V DC or +24 V DC), short-circuit proof
Output "FDKB unlock" : max. 300 mA short-circuit proof
Terminals
: max. 1,5 mm
2
wire gauge, removable
Compatibility : The Interface modules may be operated on a free selectable
micro module slot of the FACP IQ8Control.
For System 8000 fire alarm control panels the MB interface
module may be used as a replacement devices.