Mini-AT User Guide
Item
No. Item Name Description
————————————————————————————————————————
143 PCOR PRESS LOW ALARM
This item (143) indicates if a low PCor pressure alarm was
generated.
During a wake cycle, if the measurement for item 008
(PCor GAS PRESSURE) is a value less than the value entered at
item 011 (PCor PRES LOLIM), an alarm is initiated
and is
indicated by placing dots on the LCD and “11111111” at item
143. “00000000” at item 143 indicates there is no PCor
Pressure Low Alarm. The alarm indicators will remain active
until manually cleared (by software) or automatically when
RBX (item 165) is enabled. Also see item 105.
The PCor
Pressure Low Limit value (item 011) is user selectable and is
normally set somewhere between 0 and 50% of transducer range.
Default = 00000000
144 TEMP LOW ALARM
This item (144) indicates if a low temperature alarm was
generated.
During a wake cycle, if the measurement for item 026
(GAS TEMPERATURE) is a value less than the value entered at
item 027 (TEMP LOLIM), an alarm is initiated
and is indicated
by placing dots on the LCD and “11111111” at item 144.
“00000000” at item 144 indicates there is no Temperature Low
Alarm. The alarm indicators will remain active until manually
cleared (by software) or automatically when RBX (item 165) is
enabled. Also see item 106.
The
Temperature
Low Limit value
(item 027) is user selectable and is normally set somewhere
between 0 and 50% of transducer range.
Default = 00000000
145 PCOR PRESS HIGH ALARM
This item (145) indicates if a high PCor pressure alarm was
generated.
During a wake cycle, if the measurement for item 008
(PCor GAS PRESSURE) is a value greater than the value entered
at item 010 (PCor PRES HILIM), an alarm is initiated
and is
indicated by placing dots on the LCD and “11111111” at item
145. “00000000” at item 145 indicates there is no PCor
Pressure High Alarm. The alarm indicators will remain active
until manually cleared (by software) or automatically when
RBX (item 165) is enabled. Also see item 105.
The PCor
Pressure High Limit value (item 010) is user selectable and is
normally set somewhere between 50 and 100% of transducer
range.
Default = 00000000