Mini-AT User Guide
Item
No. Item Name Description
————————————————————————————————————————
208 AVG FLOW RATE Calculated average rate of flow for Corrected Volume (000) for the
time interval selected at item 202, expressed in CorVol units per
hour. Example: If the COR VOL UN CODE (item 090) is 7 (CCF)
and 211,704 cubic feet of corrected volume were measured during
the last log interval of 24 hours, the number displayed will be
88.21.
Default = 0.00
209 INST FLOW RATE The current instantaneous rate of flow for Corrected Volume (000),
expressed in the selected CorVol units (item 090) per hour. The
value is equal to the most recent increment of CorVol, divided by
the length of time between the last two correction cycles. (The
minimum acceptable time between correction cycles is one
minute.) If the meter is rotating faster than 1 RPM, the calculation
is delayed until the time is equal to, or is greater than, one minute.
When accessed, the unit will display the most recently computed
value.
Default = 0.00
210 PEAK FLOW RATE The highest INST FLOW RATE (item 209) during the current time
interval (item 202), expressed in CorVol units (090) per hour.
Default = 0.00
211 PEAK HOUR CORVOL The largest amount of Corrected Volume measured over a 1-hour
period during the 24 hour gas day. The 1-hour time periods are
fixed, consecutive hours, i.e., 8:00 to 9:00, 9:00 to10:00, 10:00 to
11:00, etc. They are not moving 1-hour windows.
Default = 00000000
212 PEAK HR END TIME The ending-hour time for PEAK HOUR CORVOL (item 211).
Default = 00 00 00
213 PEAK HOUR DATE Date for PEAK HR END TIME (item 212). Format: Determined
by item 262
Default 01-01-98
214 PCOR INTVL HI P Highest PCor Gas Pressure (item 008) measured during the Time
interval selected at item 202. The value at item 214 is initialized
(re-zeroed) at the beginning of each new log interval.
Default = 0.00