System faults. Faults typically related to the touchscreen controller.
SIM Status. Operating SIM status errors. See About Status indicators on page 11.
On the Error Logs screen, you can:
View one or more errors. See Viewing errors on page 79.
Clear errors. See Clearing errors on page 79.
Save an error log to an SD card or USB stick. See Backing up (exporting) error logs on
page 85.
Delete or clear all entries in an error log. See Deleting or clearing an error log on page 85.
1.4.3.6 Sensors and Channels
This screen provides information screens on:
Sensors - The Sensors status screen displays the current active value for each of the
temperature and pressure (e.g., water flow rate, VS load duty cycle and the altitude)
sensors. If a:
Temperature sensor is not connected to the controller the text ‘n/c’ is displayed.
Pressure sensor is not connected to the controller, ‘0’ is displayed.
ATD Channels - (Analog to-Digital conversion) Lists the raw, unfiltered input values from
the analog inputs.
1.4.3.7 Clear Errors
Errors are triggered when a sensor detects that the boiler is operating outside its limits. If more
than one error/alarm is present, the status bar slowly rotates though the various alarm states.
Status Bar
Color
Description
Green Normal state - boiler is operating within its limits.
Yellow Warning error - When the controller detects an error.
Red
Alarm - Unresolved condition or error detected while the boiler is firing or
preparing to fire that results in the boiler shutting down and entering a lock-out
state. To change these error lockout periods, see Changing default error
lockout time periods on page 77.
For minor errors, the boiler will lock out for 5 minutes, and then attempt
to restart automatically.
For major errors, the boiler will lock out for 60 minutes after 3
unsuccessful ignition attempts, and then attempt to restart.
Table 2 Status bar background colors
Section: Introduction and overview of the features in the V10 controller