EasyManuals Logo
Home>IBC>Controller>V-10

IBC V-10 User Manual

IBC V-10
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
61
6.0 Start-up
Note
For a boiler to fire, it needs an "enabler" across the load such as a zone valve end switch,
thermostat switch, or jumper.
When a boiler is first energized, the controller runs through a power-up sequence that takes
approximately one minute. During this time, the controller completes a self-diagnostic, and loads all
previous settings. When power is restored after a power interruption, the boiler automatically resumes
operation with all the previously stored values.
If commissioning a boiler with a new (replacement controller), see Programming a replacement
touchscreen controller on page 78.
6.1 Start-up checklist
Start-up Checklist Check
Measured the inlet gas pressure. Refer to the boiler's Installation and Operating Instructions
manual.
Tested the flue gas (combustion test). Refer to the boiler's Installation and Operating
Instructions manual.
Tested the ignition system safety shutoff device. For instructions, see Testing the ignition
safety shutoff on page 62.
Tested the Hi Limit cutoff temperature functionality to ensure the sensor is working. For
instructions, see Testing the Hi-limit temperature function on page 62.
Tested the low water cutoff functionality to ensure that the sensor is working. For
instructions, see Testing the low water cutoff (LWCO) function on page 62.
Tested the pressure relief valve. For instructions, refer to the Installation and Operating
Instructions manual "Service and maintenance: Relief valve" section.
Checked that the exhaust pipe clamp is tight and secure (no leaking flue into the room).
Refer to the Installation and Operating Instructions manual "Installation: Exhaust vent
material" section.
Tested the flow by observing the supply and return delta temperature.
Verified that the correct pump is activated by the corresponding call for heat.

Table of Contents

Other manuals for IBC V-10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC V-10 and is the answer not in the manual?

IBC V-10 Specifications

General IconGeneral
BrandIBC
ModelV-10
CategoryController
LanguageEnglish

Related product manuals