2.2.2 Advanced reset heating
Advanced Reset heating offers greater control of air temperature in a building, and can be more
accurate than standard reset heating. More parameter settings are available that allow the reset
heating curve to extend down to much lower target supply water temperatures. This is useful for
radiant heat emitters such as floors.
Configure Advanced Reset via Advanced Setup >set up a load as Reset Heating> Choose an
emitter > OK>Scroll down to Advanced Reset > tap Off > then On > Save. A list of all available
settings for Advanced Reset appear. For a list of advanced setup settings, see Operational settings in
the Advanced Setup menu: temperature ranges and defaults on page 32.
Below is an illustration of how different emitters determine the characterized heating "curve" by
delivering heat to an area at a different rate or amount as the outdoor temperature changes.
Figure 8 Characterized heating curve in advanced reset heating
Fin-tube baseboard
IBC Air handler
Cast iron radiator
Low mass radiant floor
High mass radiant floor