EasyManuals Logo
Home>Inovance>Controller>AM600 Series

Inovance AM600 Series Hardware Manual

Inovance AM600 Series
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
-13-
Introduction
3) Guide rail: The AM600 series use a modularized structure. The power module
,
CPU module
,
and
expansion modules must be installed on the guide rail and then 󶍾xed to the corresponding plane.
Note: Use the standard DIN35 guide rail and ensure that it is not deformed or painted with isolating
vanish and that its electrical conductivity is excellent. You can buy the guide rail yourself.
In addition to the preceding modules
,
you can select expansion modules based on requirements to build
the local or remote control system. For details about the local expansion modules
,
remote expansion
modules
,
and module wiring
,
see Section
"2.1.2 Functions of Local Expansion Modules"
,
Section
"2.1.3
Functions of Remote Expansion Modules"
,
and
"Chapter 5 Wiring"
respectively.
2.1.1 Functions of the CPU Module
CPU Module
Model
Local
Expansion
Module
Count
[1]
Program
Storage
Space
Data
Storage
Space
Number
of Axes
High-
speed I/O
Function
Output
Type
Communication
RS485 LAN EtherCAT Pro󶍾bus-DP
CANopen/
CANlink
Modbus/
TCP
Modbus
(serial)
AM401-
CPU1608TP
8 4 MB 8 MB
4
Built-in
16-in-
8-out
high-
speed
I/ O
Source
output
(1
channel)
(1
channel)
(Supports
125
stations.)
× × ×
AM402-
CPU1608TP
8
× × ×
AM401-
CPU1608TN
4
Sink
output
(1
channel)
(1
channel)
× × ×
AM402-
CPU1608TN
8
× × ×
AM600-
CPU1608TP
16
4 MB 8 MB
32
Built-in
16-in-
8-out
high-
speed
I/ O
Source
output
(2
channels)
(1
channel)
(Supports
125
stations.)
×
(Number of
supported
stations up
to 63)
× ×
AM610-
CPU1608TP
to M8306
16
×
Source
output
(2
channels
(1
channels
×
(Number of
supported
stations up
to 31)
×
[1] The power module and end cover are excluded.
Note that models AM401 and AM402 are not available for European market.
Communication ports of the CPU module
Communication
Ports of the CPU
Module
Communication
Protocol
Cable Application Matching Module
CN1 Modbus-RTU DB9 Two RS485 ports
,
supporting the Modbus protocol -
CN2
Pro󶍾bus-DP DB9 The maximum Pro󶍾bus-DP baud rate of is 12 Mbit/s. AM600-RTU-DP
CANopen/CANlink DB9
Inovance CANlink/CANopen industrial control network.
The maximum CAN communication rate is 1 Mbit/s.
AM600-RTU-COP
CN3
Ethernet protocol
and Modbus-TCP
Network
cable
Host PC or HMI communication/remote monitoring/data
exchange/industrial control network
-

Table of Contents

Other manuals for Inovance AM600 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance AM600 Series and is the answer not in the manual?

Inovance AM600 Series Specifications

General IconGeneral
BrandInovance
ModelAM600 Series
CategoryController
LanguageEnglish

Related product manuals