GD200A series VFD Function parameters
-97-
Function
code
Name
Description
Default
value
Modify
P24.01
Press feedback
source
0: AI1 setting value (implemented through the
analog potentiometer on the keypad for the
0150G/018P and lower models; not available for
the 018G/022P and higher models.)
1: AI2 setting value
2: AI3 setting value
3: HDI setting value
0
P24.02
Hibernation
check
0: Hibernate as the setting frequencyP24.03
1: Hibernate as the feedback pressureP24.04
0
P24.03
Starting
frequency of
the hibernation
0.00P00.03 (the max. frequency)
10.00
Hz
P24.04
Starting
pressure of
hibernation
0.00100.0%
50.0%
P24.05
Hibernation
delay time
0.03600.0s
5.0s
P24.06
Hibernation
awake
0: Awake as the setting frequencyP24.07
1: Awake as the feedback pressureP24.08
0
P24.07
Awake
frequency
0.00P00.03 (the max. frequency)
20.00
Hz
P24.08
Setting value of
hibernation
awake
0.00100.0%
10.0%
P24.09
Min.
hibernation
time
0.03600.0s
5.0s
P24.10
Valid auxiliary
motor
P24.10P24.12 can make three motors to form a
simple system of water supply.
0
P24.11
Start/stop delay
time of auxiliary
motor 1
5.0s
P24.12
Start/stop delay
time of auxiliary
motor 2
5.0s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive200A Series and is the answer not in the manual?

INVT Goodrive200A Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive200A Series
CategoryDC Drives
LanguageEnglish

Related product manuals