8.2.1 Commissioning
1. Imporng IO devices into the control conguraon:
1. Select the "Add device" command in the context menu of the target system (device,
Lenze controller, ...) to extend the control conguraon with the IO device.
2. Name the inserted IO device sensibly.
You can enter a name by clicking on the element. The names must only contain
the characters "A ... Z", "a ... z", "0 ... 9" or "_" and must not begin with a digit.
3. Execute the "Add device" command in the context menu of the IO device.
4. In the dialog box that appears, select the I/O modules to be used for the IO device and
add it to the IO device by clicking the "Add device" buon.
5. Set the IP address, subnet mask, gateway address and the staon name of the IO device
in the PROFINET parameters (Fieldbus secon).
2. Load the network conguraon into the master:
1.
Log o: Menu command Online à Log o or <Ctrl>+<F8>.
2.
Compile: Menu command "Build à Compile" or <F11>.
3.
Log in: Menu command "Online à Log in" or <Alt>+<F8>.
The conguraon, the parameter sengs and the PLC program are loaded into the IO
controller. Aerwards, all IO devices are inialized.
These steps must be carried out aer every change within
the »PLC Designer« project. An already exisng conguraon and an exisng
PLC program in the IO controller will be then overwrien.
8.2.1.1 Restarng or stopping the communicaon
The communicaon needs to be restarted aer changes to the interface conguraon (e. g.
staon address and IP conguraon) so the changed sengs become eecve without
switching the voltage.
4Staon name and IP conguraon ^ 74
There are two opons for restarng the communicaon:
Set 0x2380 to 1 (restart with current values)
Set 0x2380 to 2 (restart with the values saved last)
The following opon can be used to stop communicaon:
Set 0x2380 to 5 (stop network communicaon)
Parameter
Address Name / seng range / [default seng] Informaon
0x2380 PROFINET communicaon Restart / stop communicaon
When the device command has been executed successfully, the value
0 is shown.
0 No acon/no error Only status feedback
1 Restart with current values Restart communicaon with the current values.
2 Restart with stored values Restart communicaon with the values of the PROFINET parameters that
have been saved last (0x2381:001 ... 0x2381:009).
5 Stop network communicaon Stop communicaon
10 In progress Only status feedback
11 Acon cancelled
12 Fault
Conguring the network
PROFINET
Commissioning
72

Table of Contents

Other manuals for Lenze C520

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze C520 and is the answer not in the manual?

Lenze C520 Specifications

General IconGeneral
BrandLenze
ModelC520
CategoryController
LanguageEnglish

Related product manuals