Address Name / seng range / [default seng] Informaon
0x231F:002 Communicaon module ID: Module ID connected
•
Read only
Display of the network opons currently available in the device.
Note!
When switched on, the device checks whether the parameter sengs
saved in the memory module match the device hardware and rmware.
In case of an incompability, a corresponding is error message is output.
48 No network
65 AS-Interface
67 CANopen
71 EtherNet/IP
72 BACnet
78 POWERLINK
80 PROFIBUS
82 PROFINET The controller currently supports these network opons.
84 EtherCAT
86 Modbus TCP/IP
87 Modbus
11.3.3 Service life diagnoscs
Current values on the operang me and temperatures of the controller can be read out.
Parameter
Address Name / seng range / [default seng] Informaon
0x2D81:001 Life-diagnosis: Operang me
•
Read only: x s
Display showing for how long the device has been running so far. The
counter cannot be reset.
0x2D81:002 Life-diagnosis: Power-on me
•
Read only: x s
Display showing for how long the device has been supplied with line
voltage so far.
0x2D81:004 Life-diagnosis: Main switching cycles
•
Read only
Display of the number of switching cycles of the mains voltage.
11.4 Error handling
Error messages can be reset.
Parameter
Address Name / seng range / [default seng] Informaon
0x2841 Reset error
0 ... [0] ... 1
1 ≡ reset error (error acknowledgement)
Diagnoscs and fault eliminaon
Error handling
Service life diagnoscs
97