Commissioning
Parameter setting with the XT EMZ9371BC keypad
Commissioning example in V/f characteristic control mode
6
6.3
6.3.1
6.3-1
EDSVF9333V EN 3.0-06/2005
6.3 Parameter setting with the XT EMZ9371BC keypad
6.3.1 Commissioning example in V/f characteristic control mode
The example describes how to commission a speed control for the controller
with power-related three-phase asynchronous motor.
Switch-on sequence Note
1. Insert the keypad
2. Ensure that the controller is inhibited after
switching on the mains
misc008
59 28
X5
}
TerminalX5/28=LOW
(see chapter ”Commissioning”
”controller inhibit”)
3. Ensure that no external error is active Terminal X5/E4 = HIGH
4. Switch on
A The control card is supplied via an external voltage:
Switch on the external DC 24 V supply voltage
ON
misc002
B The control card is supplied via the internal voltage:
Switch on the mains. The controller provides the
DC 24 V supply.
5. After approx. 2 s the controller is initialised and the
keypad is in the operating level and displays the
current speed (C0051)
9371BC004
d ABbc
0050
00
0.00 Hz
0%
6. Change to the ”Terminal I/O” menu and configure
the function of the control terminals to adapt them
to your application.
Lenze setting: C0005 = 1000 (basic configuration
”speed control”)
UseC0002=0torestoretheLenze
setting
(see chapter ”Commissioning”
”Change assignment of the control
terminal X5 and X6”)
7. For quick commissioning select the menu ”Short
setup”
d ABbc
p
SHPRG
Para
Code
Menu
4
2
Quick start
V/f quick
9371BC007
The submenu ”Setup V/f” contains the
codes that are required for
commissioning a standard application.
The digital inputs are configured in the
Lenze setting:
X5/E1: Deactivate CW rotation/quick
stop
X5/E2: Deactivate CCW rotation/quick
stop
X5/E3: Activate fixed setpoint 1 (JOG1)
X5/E4:Seterrormessage(TRIPSET)
X5/E5: Reset error message (TRIP
RESET)
(see chapter ”Parameter setting”)
A Use to change to the menu level
B Use to change to the menu ”Short setup”
and then to the submenu ”Setup V/f”
C Use to change to the code level to parameterise
your drive
YZ
y
z
T
V
S
U
d ABbc
p
SHPRG
Para
Code
Menu
0034
00
0
AIN1 range
9371BC008
8. Adapt the controller to the mains (C0173)
Lenze setting: 1 (400 V mains voltage)
9. Only for the variants V060, V110, V270, V300 in the
power range of 110 ... 400 kW:
Adapt the brake transistor threshold (C0174)
Lenze setting: 3 (500 V mains voltage, 885 V brake
voltage)
Seecodetable
10. Enter the motor data See motor nameplate and chapter
”Commissioning” ”Adapt motor
data”
A If you use a Lenze motor:
Select the motor type connected under C0086.
The data of the Lenze motors are saved
under C0086.
B If you do not use a Lenze motor:
Enter the data of the motor nameplate
z Rated motor power (C0081)
Lenze setting: device-dependent