Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8
8.2
8.2.7
8.2-55
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0148
ident run 0
0 WRK
stop
Ready
Motor data identification
1. Inhibit controller, wait until
drive has stopped
2. Enter the correct values of the
motor nameplate into C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
4. Enable controller
The identification
–starts, goes off. The
motor ”whistles” but does
not rotate!
lastsapprox.1...2min
is completed when is lit
again
5. Inhibit controller:
6.6-13
1 WRK
run
Start identification
C0234 damp value 20 -100 {1 %} 100 Influence of the oscillation
damping, function block MCTRL
z Minimising a tendency to
oscillation of the drive
z Influences the tendency to
oscillation of the drive
z When C0025 >1 and C0006 = 1,
C0234 is set to 0
8.2-25
8.2-48
C0235 damping 5 1 {1 ms} 600 Filter time of the oscillation
damping, function block MCTRL
z Filter time for the internal
signal for oscillation damping
8.2-25
8.2-48
C0236 damp limit 0.2 0.0 {0.1 Hz} 20.0 Limit value of oscillation damping,
function block MCTRL
z Limit value for the internal
signal of oscillation damping
C0420
ENCODER
CONST
512 1 {1 inc/rev} 8192 Number of increments for
incremental encoder at X8 or X9
z Connect incremental encoders
with HTL-level on X9 only
6.7-1
C0421
ENC VOLTAGE 5.00 5.00 {0.1 V} 8.00 Supply voltage for the incremental
encoder at X8
CAUTION! A wrong entry can
destroy the incremental encoder!
C0497 Nact filter 2.0 0.0 {0.1 ms} 50.0 Filter time constant N
act
for actual
speed value, function block
MCTRL2
z Internal filtering of the speed
signal for control
z C0497=0ms:Switchedoff
8.2-48
C0890
CFG: N-SET 5050 NSET-NOUT Selection list 1 Configuration of analog input
signal, function block MCTRL
z Speed setpoint
8.2-25
8.2-48
C0891
cfg: M-add 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MCTRL
z Additional torque setpoint or
torque setpoint
8.2-48
C0892
cfg: lo-M-lim 5700 ANEG1-OUT Selection list 1 Configuration of analog input
signal, function block MCTRL
z Lower torque limit in [%] of
C0057
C0893
cfg: hi-M-lim 19523 FCODE-472/3 Selection list 1 Configuration of analog input
signal, function block MCTRL
z Upper torque limit in [%] of
C0057