Commissioning
Optimising the operating behaviour
Boost correction with V/f characteristic control
6
6.11
6.11.3
6.11-6
EDSVF9333V EN 3.0-06/2005
Stop!
A longer operation of the motor in standstill may destroy the
motor by overheating, especially in case of small motors.
ƒ Connect the thermal contact (NC contact), PTC, or KTY of the
motor and activate the motor temperature monitoring of the
controller.
ƒ Operate self-ventilated motors with a blower, if required.
Setting voltage boost
1. Set a voltage boost in C0016. ( 6.8-6)
–WhenC0016=0%noboostispossible.
2. For magnetising the motor, consider enough time from controller
enable to the start of the speed ramp-function generator.
The bigger the motor the longer the time for magnetisation. A motor
with the power of 90 kW requires up to 2 s.
If the desired continuous current does not flow, correct the boost
using the codes C0080, C0095 and C1583.
Carry out a boost correction
3. If required, set the desired motor magnetising current (standstill
current) in C0095 which is to be achieved by the boost correction.
The value in the Lenze setting has been evaluated by the controller
from the entered motor data of the motor nameplate.
When C0095 = 0, the boost correction is deactivated.
4. Set the influence of the boost correction in C0080.
Adjustment