Configuration
Function blocks
Internal motor control with V/f characteristic control (MCTRL1)
8
8.2
8.2.6
8.2-28
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0056 MCTRL-MSET2 -100.00 {0.01 %} 100.00 Read only. The output signal
depends on the operating mode:
z Current motor current in case
of V/f characteristic control,
function block MCTRL1
z Torque setpoint in case of
vector control, function block
MCTRL2
8.2-25
8.2-48
C0058 MCTRL-FACT -600.0 {0.1 Hz} 600.0 Output frequency
z Display only
z MCTRL-FACT = 100.0 % =
1000.0 Hz
8.2-25
8.2-48
C0063 Mot temp 0 {1 °C} 200 Motor temperature
z Display only
z Monitoring of the motor
temperature must be activated.
z KTY at X8/5, X8/8:
– At 150 °C TRIP OH3 is set
– Early warning is possible via
OH7, temperature is set in
C0121
z PTC, thermal contact at T1, T2:
– If it is released, TRIP or
warning OH8
8.2-25
8.2-48
C0064 Utilisation 0 {1 %} 150 Device utilisation I×t
z Display only
z Device utilisation during the
last 180 s of operating time
z C0064 > 100 % releases
warning OC5
z C0064 >140 % limits the output
current to t he rated controller
current
8.2-25
8.2-48
C0070 Vp speed CTRL 10.0 0.0 {0.1 } 255.9 Gain of speed controller
8.2-25
8.2-48
C0071 Tn speed CTRL 50 1 {1 ms} 6000 Integral-action time of speed
controller
C0071 = 6000 ms: No
integral-action time
C0074 limit N 10.00 0.00 {0.01 %} 100.00 Limitation of the speed controller
z Influence of the speed
controller for V/f characteristic
control with feedback
z max. setpoint difference in
percent
8.2-25
8.2-48
C0075 Vp curr CTRL 0.20 0.00 {0.01 } 0.99 Gain of current controller
z Vector control: gain of current
controller
z V/f characteristic control:
maximum current controller
8.2-25
8.2-48
C0076 Tn curr CTRL 10.0 0.1 {0.1 ms} 2000.0 Integral-action time of current
controller
z Vector control: integral-action
time of current controller
z V/f characteristic control:
maximum current controller
z C0076 = 2000 ms: current
controller is switched off
8.2-25