3.1 General data/operating conditions
Field Values
Conformity CE Low-Voltage Directive (73/23/EEC)
Approvals
UL508C Power Conversion Equipment
Underwriter Laboratories (File No. E132659)
for USA and Canada
(drive controller of variants V024 and V100 on mains with
earthed external conductor are not UL-approved)
Max. permissible
cable cross-section
At rated mains voltage and a switching frequency of ≤ 8kHzwithout
additional output filter
shielded 50 m
For compliance with EMC regulations, the permissible cable
lengths must be changed.
unshielded 100 m
Vibration resistance Germanischer Lloyd, general conditions
Climatic conditions Class 3K3 to EN50178 (without condensation, average relative humidity
85%)
Degree of pollution VDE 0110 part 2 pollution degree 2
Permissible
temperature ranges
Transport -25 °C... +70 °C
Storage -25 °C... +55 °C
Operation
EVF9321 ... EVF9326 0 °C ... +55 °C
Reduce the rated output current
by 2.5%/ °C above +40 °C
EVF9327 ... EVF9333 0 °C ... +50 °C
Permissible
installation height
0 ... 4000 m amsl Above 1000 m reduce the rated output current by
5 %/ 1000 m
Above 2000 m the use is only permitted in
environments with overvoltage category II
Mounting position Vertical
DC-bus operation Possible