Configuration
Code table
8
8.3
8.3-7
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0057 MAX TORQUE 0 {1 Nm} 500 Maximum torque
z Read only
z Maximum possible torque of
the drive configuration
z In case of V/f characteristic
control depending on C0022,
C0086, C0088
z In case of vector control
depending on C0022, C0086,
C0088, C0091
C0058 MCTRL-FACT -600.0 {0.1 Hz} 600.0 Output frequency
z Display only
z MCTRL-FACT = 100.0 % =
1000.0 Hz
8.2-25
8.2-48
C0059 Mot pole no. 1 {1} 50 Pole pair number of the motor
z Display only
C0061 HEATSINK TEMP 0 {1 °C} 100 Heatsink temperature
z Read only
z If the temperature of the
heatsink > 85 °C the controller
sets TRIP OH
z Early warning is possible via
OH4, temperature is set in
C0122
See System
Manual
(extension)
C0063 Mot temp 0 {1 °C} 200 Motor temperature
z Display only
z Monitoring of the motor
temperature must be
activated.
z KTY at X8/5, X8/8:
– At 150 °C TRIP OH3 is set
– Early warning is possible via
OH7, temperature is set in
C0121
z PTC, thermal contact at T1, T2:
– If it is released, TRIP or
warning OH8
8.2-25
8.2-48
C0064 Utilisation 0 {1 %} 150 Device utilisation I×t
z Display only
z Device utilisation during the
last 180 s of operating time
z C0064 > 100 % releases
warning OC5
z C0064 >140 % limits the
output current to the rated
controller current
8.2-25
8.2-48
C0067 Act trip Selection list 10 Momentary fault message
z Display only
C0070 Vp speed CTRL 10.0 0.0 {0.1 } 255.9 Gain of speed controller
8.2-25
8.2-48
C0071 Tn speed CTRL 50 1 {1 ms} 6000 Integral-action time of speed
controller
C0071 = 6000 ms: No
integral-action time
C0074 limit N 10.00 0.00 {0.01 %} 100.00 Limitation of the speed controller
z Influence of the speed
controller for V/f characteristic
control with feedback
z max. setpoint difference in
percent
8.2-25
8.2-48