EasyManuals Logo
Home>Notifier>Control Panel>AFP-400

Notifier AFP-400 Installation Manual

Notifier AFP-400
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #163 background imageLoading...
Page #163 background image
AFP-300/AFP-400 Installation50253 PN 50253:C1 05/22/97 A-1
$SSHQGL[$$QQXQFLDWRUV
2YHUYLHZ
Appendix A contains the following information:
Tables necessary for configuring the annunciator display; and
Typical annunciator wiring diagrams.
Note that Appendix A contains information specific to the AFP-300/AFP-400 only. For
complete annunciator installation information, refer to the respective annunciator
manual.
$QQXQFLDWRU,QWHUIDFHV
The control panel provides Terminal Mode (LCD-80) and ACS Mode Interfaces that
provide high speed, two-way communication link to multiple annunciators. You can
locate annunciators up to 6,000 feet from the control panel.
7HUPLQDO0RGH/&'
Use the Terminal Mode Interface for communicating with LCD-80 Annunciators
operating in Terminal Mode (through TB3 on the CPU). In Terminal Mode, each
LCD-80 display mirrors the AFP-300/AFP-400 front panel display. Each LCD-80
displays the complete status of the fire alarm system and lets you do Acknowledge,
Silence, and System Reset control panel functions from a remote location.
$&60RGH
Use the ACS Mode Interface (through TB4 on the CPU) for communicating with the
following LED/Lamp type annunciators: ACM-16AT, AEM-16AT, ACM-32A,
AEM-32A, AFM-16A, AFM-32A, AFM-16AT, LDM-32, LDM-E32, and LDM-R32.
The ACS interface also communicates with the AMG-1 Audio Message Generator, the
UZC-256 Universal Zone Coder, the NIB-96 Network Interface Board, the LCD-80
Annunciators operating in the ACS Mode and the ACM-8R Relay Annunciator
Module.
The ACM-8R Relay Module provides relays for controlling equipment located at
remote locations. The ACM-8R greatly increases the relay control capabilities of the
control panel. You can assign the ACM-8R to any of the 576 panel annunciation points.
Each ACM-8R module covers continuous groups of eight panel points.
The ACS Mode Interface can annunciate CPU, zone, detector, module, and circuit
status. The 576 panel annunciation points are divided into nine groups of 64 points, as
shown in Table A-2 through Table A-10. Each group can be assigned to one or more of
the ten annunciator addresses supported by the control panel.
The control panel uses ACS annunciator addresses 1-19 without a UDACT and ACS
annunciator addresses 1–10 with a UDACT. Each address can communicate with one
receive/transmit device. Configure other devices on the same address as Receive Only.
You can connect up to 32 devices to the ACS output, all addresses combined.
Use the ACS Mode Interface to Acknowledge, Silence, Drill, and Reset the control
panel from a remote location. The ACS Mode Interface can also activate output circuits
and control modules from remote locations.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-400 and is the answer not in the manual?

Notifier AFP-400 Specifications

General IconGeneral
BrandNotifier
ModelAFP-400
CategoryControl Panel
LanguageEnglish

Related product manuals