7-4-3
Trip Retry Operation
This function is used to set the operation selection to trip retry.
Parameter No. Function name Data
Default da-
ta
Unit
E139
Overvoltage/Overcurrent
Restart Function Selection
0: Trip
0 -
4: Restart at the frequency selected
by E152
H04 Retry Count at Trip 
0: Disable
0 Times
1 to 20: Number of retries
H05 Retry Standby Time at Trip 0.5 to 20.0 5.0 s
E20, E21, E27
Output Terminal [DO1]
Function Selection, Output
T
erminal [DO2] Function
Selection, Output Terminal
[ROA, ROB] Function Se-
lection
26: TR
Y (Auto-resetting) - -
Overvoltage/Overcurrent Restart Function Selection (E139)
E139 data
Operation details
Without auto search
With auto search
*1
0: Trip An alarm is output when an overvoltage or overcurrent is detected, the inverter
output is cut of
f, and the motor falls in a free-run state.
4: Restart based on pull-in
frequency
If an overvoltage or overcurrent is detected, the inverter output is cut off, and the
motor falls in a free-run state.
During recovery from overvoltage or
overcurrent, restart is performed from
the pull-in frequency. Select the pull-in
frequency in E152.
During recovery from overvoltage or
overcurrent, auto search is performed,
the motor speed is estimated, and re-
start is performed from the frequency.
*1. With auto search is selected when Enable auto search for idling motor speed at starting “STM” is ON, or
H09 (d67) = 2.
When a motor control method with speed sensor is selected, restart is performed from the motor speed de-
tected by the speed sensor. In the case of a motor control method without speed sensor, restart is per-
formed from the estimated speed.
Additional Information
When using vector control without speed sensor, do not use restarting from the pull-in frequen-
cy (Starting Frequency Selection at Frequency Pull-in Restart (E152)). If you select starting
from pull-in frequency, normal start may not be performed, or the device may be damaged.
Use the retry function to recover from overvoltage or overcurrent.
(H04: Retry Count at Trip, H05: Retry Standby Time at T
rip)
As for the starting method, the settings in E139 is applied.
7 Other Functions
7-58
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
BrandOmron
ModelM1 Series
CategoryInverter
LanguageEnglish

Related product manuals