! Matrix 832 / 832+ / 424
RINS428-5 Page 85
Activation
When an event occurs the MX-VOICE transmits the related voice message to the alarm event.
SUPPLY
FAU L T
ARMED
P.A.READY
TAMPER
FIRE
DAY
ALARM
8
8
BCD
2
1
34
ET
FUNC
P.
.
FIRE
5678
90
Keypad Programming Procedure
8.3.1 Disarmed Mode Events Send Options
Enter BY followed by one digit for the desired partition number from [1 - 4]. To choose an option use
the
> and ? buttons. To change an option setting, press the C button. To save the changes press B. An
acceptance tone will be heard.
Option Option Off = Alarm LED Off Option On = Alarm LED On Default
1 Alarms are not sent Alarms are sent On
2 PA are not sent PA are sent On
3 Fire are not sent Fire are sent On
4 Maintenance are not sent Maintenance are sent On
5 Open/Close are not sent Open/Close are sent On
6 Medical not sent Medical are sent On
7 Confirmed alarm not sent Confirmed alarm sent Off
8 Omits (Bypass) not sent Omits (Bypass) sent Off
8.3.2 Arm Mode A Events Send Options
Enter BY followed by one digit for the desired partition number from [1 - 4]. To choose an option use
the
> and ? buttons. To change an option setting, press the C button. To save the changes press B. An
acceptance tone will be heard.
Option Option Off = Alarm LED Off Option On = Alarm LED On Default
1 Alarms are not sent Alarms are sent On
2 PA are not sent PA are sent On
3 Fire are not sent Fire are sent On
4 Maintenance are not sent Maintenance are sent On
5 Open/Close are not sent Open/Close are sent Off
6 Medical not sent Medical are sent On
7 Confirmed alarm not sent Confirmed alarm sent Off
8 Omits (Bypass) not sent Omits (Bypass) sent Off
8.3.3 Arm Mode B Events Send Options
Enter BYT followed by one digit for the desired partition number from [1 - 4]. To choose an option use
the
> and ? buttons. To change an option setting, press the C button. To save the changes press B. An
acceptance tone will be heard.
Option Option Off = Alarm LED Off Option On = Alarm LED On Default
1 Alarms are not sent Alarms are sent On
2 PA are not sent PA are sent On
3 Fire are not sent Fire are sent On
4 Maintenance are not sent Maintenance are sent On
5 Open/Close are not sent Open/Close are sent Off
6 Medical not sent Medical are sent On
7 Confirmed alarm not sent Confirmed alarm sent Off
8 Omits (Bypass) not sent Omits (Bypass) sent Off