Maintenance and service
5.2 Replacing modules (spare part scenario)
SIMOTION D410
Commissioning Manual, 02/2012
169
Automatic upgrading/downgrading (FW update)
When starting up, the system automatically upgrades or downgrades all DRIVE-CLiQ
components to the version of the component firmware on the CompactFlash Card.
Components that cannot be downgraded to the component firmware version on the
CompactFlash Card (for example, old firmware on the CompactFlash Card and new
components to which the old firmware cannot be loaded) retain their firmware version. The
resulting firmware version combinations are always functional.
The component version can be obtained from the CONTENT.TXT file in the main directory of
the CF card.
Note
During an automatic FW update, please take note of the messages and alarms in the
SIMOTION SCOUT detail window.
An FW update on the D410 is signaled by the RDY LED flashing yellow, while on the DRIVE-
CLiQ components (TM, SMC, etc.) it is signaled by the RDY LED flashing red/green.
FW update running: RDY LED flashes slowly (0.5 Hz)
FW update complete: RDY LED flashes quickly (2 Hz)
Go offline once all the FW updates are complete, then switch the 24 V supply for the
upgraded/downgraded initialization components off/on.
The update function can be deactivated using CU parameter p7826 in the expert list.
Additional references
For additional information about this topic, consult the
SINAMICS S120
Commissioning
Manual.
See also
Update via CF card (Page 190)
5.2.4 Replacing the fan
Prerequisite
Replace the fan if a warning is output by the temperature monitoring function as a result of a
fan defect.
The SIMOTION D410 fans switch on depending on the internal module temperature. If the
temperature reaches impermissible values, this is signaled by a warning at the drive end:
A1009: CU warning: Control Unit overtemperature
In this case, the temperature (CU parameter r0037[0]) of the SIMOTION D410 has exceeded
the specified limit value.

Table of Contents

Other manuals for Siemens SIMOTION D410 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D410 DP and is the answer not in the manual?

Siemens SIMOTION D410 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D410 DP
CategoryControl Unit
LanguageEnglish

Related product manuals