EasyManuals Logo
Home>Siemens>Accessories>SIWAREX WP321

Siemens SIWAREX WP321 Manual

Siemens SIWAREX WP321
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
Technical data
12.2 Electrical, EMC and climatic requirements
SIWAREX WP321
Manual, 07/2014, A5E33715669A-02
111
Electromagnetic compatibility
Table 12- 1 Interference emission (industrial area): EN 61000-6-4
Comments
Standard
Limits
Emission of radio interferences
(electromagnetic fields)
Class A industrial environment:
EN 61000-6-4
IEC/CISPR 16-2-3: 2008
30 ... 230 MHz,
40 dB (μV/m) Q
230 ... 1 000 MHz,
47 dB (μV/m) Q
Emission on power supply ca-
bles 24 V
Class A: Industrial environment:
EN 61000-6-4
IEC/CISPR 16-2-1: 2010;
EN 55016-2-1: 2009
Class A: Industrial environment
0,15 ... 0.5 MHz, 79 dB (μV)
Q
0,15 ... 0.5 MHz, 66 dB (μV)
M
0.5 ... 30 MHz, 73 dB (μV) Q
0.5 ... 30 MHz, 60 dB (μV) M