EasyManuals Logo
Home>Siemens>Accessories>SIWAREX WP321

Siemens SIWAREX WP321 Manual

Siemens SIWAREX WP321
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
Messages
9.5 Message list
SIWAREX WP321
Manual, 07/2014, A5E33715669A-02
87
9.5
Message list
The message list is an overview of all messages that the SIWAREX module can generate. A
message can be quickly identified by the message code (number).
9.5.1
System status message list
Operator error (code 1000 to 1999)
Error code
Description and remedy
1000 operating error exists 1000 Group message, at least one operating error exists.
1001 Watchdog 1001 Watchdog, error is displayed for at least 10 seconds. A seri-
ous error has occurred in the function of SIWAREX, e.g.
program error, severe electromagnetic influence on device,
etc.
Contact the SIWAREX Support if the error occurs multiple
times.
1002 RAM error 1002 RAM error. An error has occurred in the memory; the memory
content is no longer correct. The module must be switched
off. If the error occurs again, SIWAREX is defective.
1003 Checksum incorrect parameter 1003 Checksum error at parameter. Critical error because the
parameters are no longer safe.
1004 Checksum incorrect program 1004 Checksum error program code. Critical error because the
program is no longer safe.
1102 ADU error 1102 AD converter error when reading in the measured value. If
the error occurs again, make sure that the EMC recommen-
dations are observed (chapter EMC-compliant setup
(Page 20)).
1104 Undervoltage 1104 Undervoltage at sensor cables
1105 Overload 1105 Overload of scale (ca. 110%)
1106 Underload 1106 Underload of scale (ca. -10%)
9.5.2
Technology error message list
Technology error (code 2000 to 4999)
Error code
Description and remedy
2000 Technology error exists 2000 Group message, at least one technology error exists
2001 Taring/zeroing timeout 2001 Taring of scale or set to zero is not possible because a standstill
was not reached during the standstill time. The command was
discarded.

Table of Contents

Other manuals for Siemens SIWAREX WP321

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WP321 and is the answer not in the manual?

Siemens SIWAREX WP321 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WP321
CategoryAccessories
LanguageEnglish

Related product manuals