The commands for the electronic weighing system described here can be transmitted by
several interfaces:
● by the Operator Panel via the controller to the SIWAREX module
● by SIWATOOL directly to the SIWAREX module
A data or command error is signaled if a command cannot be executed or if the sent data
record is rejected.
1 Service mode On Turn on service mode x
2 Service mode Off Turn off service mode x
11 Load factory setting The command resets the SIWAREX to the "Ex fac-
tory" status:
- All parameters and saved data are loaded with the
default values.
- All message buffers are reset.
x
60 Calibration point 0 valid Calibration point 0 valid / save values for calibration
point 0.
x
61 Calibration point 1 valid Calibration point 1 valid / save values for calibration
point 1.
x
62 Calibration point 2 valid Calibration point 2 valid / save values for calibration
point 2.
x
81 Characteristic shift Move calibration characteristic. The command de-
fines the current weight of the scale as the new zero
point (0 kg) and shifts the complete characteristic
without changing the gradient.
The command can be used, for example, in order to
compensate parts used for mounting calibration
weights on the scale at the end of the calibration.
x
82 Perform automatic calibration
Calculation of scale characteristic using the load cell
parameters from data record 10. The calculated
characteristic is entered directly in data records 3
and 4 and thus immediately enabled following exe-
cution of the command. The scale must be empty
when the command is executed.
x