Mounting
5.4 Configuration of the hardware in SIMATIC
SIWAREX WP321
24 Manual, 07/2014, A5E33715669A-02
5.4
Configuration of the hardware in SIMATIC
A station has a maximum width of 1 m, and you can use up to 64 modules depending on the
type of PN head-end, or up to 15 modules with the Profibus version. Observe the system
conditions when planning the configuration.
Each SIWAREX electronic weighing system requires 16 bytes of the I/O area. Address
assignment is carried out in the TIA Portal or in the SIMATIC Manager during hardware
configuration.