Commissioning
7.3 5-minute quick start with the operator panel and the Ready-for-Use software
SIWAREX WP321
38 Manual, 07/2014, A5E33715669A-02
Performing the automatic calibration
Figure 7-7 Quick start step 5b
Subsequently enter the "Perform automatic calibration" command with the scale empty. The
scale is calibrated directly, and clicking on the house icon returns you to the start screen.
Checking the scale following calibration
If the scale is only used for company-internal purposes, a simple check is sufficient.
Perform the following steps:
1. The scale is unloaded and shows "0 kg".
2. Place a known reference weight on the scale.
Check the displayed value.
3. If a second known reference weight is available, place it on the scale in addition.
Check whether the scale displays the sum of the reference weights.
4. Remove the reference weights from the scale.
Check that the display is "0 kg" again.