AnteRm Alarm Menu
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT VALUE
Anteroom Negative
High Alarm
Neg Hi Alm
The Neg Hi Alm item sets the negative high pressure
alarm setpoint. A high alarm condition is defined as when
the room is more negative than the Neg Hi Alm setpoint.
This item is active when the TSI key switch is in negative
room pressure position or when NEGATIVE is selected in
Room Mode item. However, it is always accessible
through the menu system.
-0.19500 in. W.C. to
+0.19500 in. W.C.
(TSI SENSOR)
-1.0 in W.C. to
+1.0 in W.C.
(PRESSURE
TRANSDUCER)
NOTE
Neg Hi Alm
cannot be set less
negative than the
Neg Low Alm
-0.1.0 in. W.C.
Anteroom Positive
Low Alarm
Pos Low Alm
The Pos Low Alm item sets the positive low pressure
alarm setpoint. A low alarm condition is defined as when
the room is less positive than the Pos Low Alm setpoint.
This item is active when the TSI key switch is in positive
room pressure position or when POSITIVE is selected in
Room Mode item. However, it is always accessible
through the menu system.
-0.19500 in. W.C. to
+0.19500 in. W.C.
(TSI SENSOR)
-1.0 in W.C. to
+1.0 in W.C.
(PRESSURE
TRANSDUCER)
NOTE
Pos Low Alm
cannot be set more
positive than the
Pos Hi Alm
+0.01.0 in. W.C.

Table of Contents

Other manuals for TSI Instruments PRESSURA RPC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments PRESSURA RPC30 and is the answer not in the manual?

TSI Instruments PRESSURA RPC30 Specifications

General IconGeneral
BrandTSI Instruments
ModelPRESSURA RPC30
CategoryController
LanguageEnglish

Related product manuals