Network
Communications
Protocol
The Comm Type item selects the communications protocol
used to interface with the building management system.
NOTE: LON can only be selected on the
Model RPC30-LON.
The Address item sets the main network address of the
room pressure controller. Each unit on the network must
have its own unique address.
NOTE: The Address item is only functional when
Comm Type is set to Modbus or BACnet.
Modbus: 1 TO 247
BACnet: 1 to 128
NOTE: Changes to the Address may take up to 1 minute to
take effect when using BACnet communications.
The MAC ID item is the Device ID of the unit for BACnet
communications.
NOTE: The MAC ID item is only functional when
Comm Type is set to BACnet.
NOTE: Changes to the MAC ID may take up to 1 minute to
take effect when using BACnet communications.
The Baud Rate item sets the communication speed of the
PresSura controller when using Modbus or BACnet
communications.
Modbus: 9600
BACnet: 9600,
19200, 38400,
76800, AutoBaud
NOTE: Changes to the Baud Rate may take up to
1 minute to take effect when using BACnet
communications.
Baud Rate is not configurable when Comm Type
is set to Modbus.