Technical Section
35
Alarm Config Menu
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Alarm Reset
Alarm Reset
The Alarm Reset item selects how the alarms terminate
after the unit returns to control set point. The Alarm Reset
affects the audible alarm, visual alarm, and relay output,
which means all are latched or unlatched.
LATCHED requires the staff to press the key to clear
alarms.
UNLATCHED (alarm follow) automatically resets the
alarm when the room pressure is:
0.001.0 in. W.C. ft/min greater than the low alarm set
point
0.001.0 in. W.C. ft/min less than the high alarm set
point
50 cfm greater than the low alarm setpoint for flow
alarms
0.3°F for temperature
0.5% RH
Latched
Unlatched
Unlatched
Enable Sound
Audible Alm
The Audible Alm item enables the beeper on the
PresSura controller.
On, Off
Off
Alarm Delay
Alarm Delay
The Alarm Delay item sets the period of time the room
pressure differential, flow or temperature must be above
the high alarm set point or below the low alarm set point
before the controller enters alarm mode. Use the
Alarm Delay function to avoid momentary, nuisance
alarms.
1 to 600 seconds
20 seconds

Table of Contents

Other manuals for TSI Instruments PRESSURA RPC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments PRESSURA RPC30 and is the answer not in the manual?

TSI Instruments PRESSURA RPC30 Specifications

General IconGeneral
BrandTSI Instruments
ModelPRESSURA RPC30
CategoryController
LanguageEnglish

Related product manuals