The Sup Cntl Dir item determines the control signal’s
output direction. As an example: if the control system
closes the supply damper instead of opening the damper,
this option will reverse the control signal to now open the
damper.
Temperature
Control Direction
The Temp Dir item determines the control signal’s output
direction. As an example: if the control system closes the
heating valve instead of opening the valve, this option will
reverse the control signal to now open the valve.
Temperature
Throttling Range
The Temp Thr item determines the throttling range, or
number of degrees that the room temperature must change
in order to go from full heating to no heating or from full
cooling to no cooling.
Temperature
Integral Time
The Temp Ti item determines the integral time of the
temperature control loop.
0.000 to 10000.000
seconds