CUR R E N T S EN S ORS PR IM AR Y T E ST ING
20 1VLG5 000 17 C
4.2.2 Installed busbars in the switchgear panel
This testing procedure includes the influence of applications such as the circuit breaker or
contactor. Installed busbars are used to make the electrical circuit between two neighboring
panels.
If high voltage cables are terminated to switchgear panel, check the installation is
dead.
Protect against any other live parts.
Step 1/5
Verify sensor parameters set in the protection relay with sensor rating plates placed on the
circuit breaker door.
Figure 29: Example of a current sensor label
On protection relay LHMI go to -> Main Menu/Configuration/Analog inputs/Current (3I, CT)
Primary current = Application nominal current
Amplitude Corr A = sensor rating plate, phase A
Amplitude Corr B = sensor rating plate, phase B
Amplitude Corr C = sensor rating plate, phase C
Nominal current = Primary current
Rated secondary Val = Rated secondary value in mV/Hz
Angle Corr A = sensor rating plate, phase A
Angle Corr B = sensor rating plate, phase B
Angle Corr C = sensor rating plate, phase C
Figure 30: Current sensor parameters

Table of Contents

Other manuals for ABB UniGear Digital

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB UniGear Digital and is the answer not in the manual?

ABB UniGear Digital Specifications

General IconGeneral
BrandABB
ModelUniGear Digital
CategorySwitch
LanguageEnglish

Related product manuals