EasyManuals Logo
Home>Allen-Bradley>Controller>Micro830

Allen-Bradley Micro830 User Manual

Allen-Bradley Micro830
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #231 background imageLoading...
Page #231 background image
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019 217
Specifications Appendix A
Micro830 48-Point Controllers
General Specifications
Attribute 2080-LC30-48AWB 2080-LC30-48QWB 2080-LC30-48QVB 2080-LC30-48QBB
Number of I/O 48 (28 inputs, 20 outputs)
Dimensions (HxWxD) 90 x 230 x 80 mm (3.54 x 9.06 x 3.15 in.)
Shipping weight, approx. 0.725 kg (1.60 lb)
Wire size 0.2…2.5 mm
2
(24…14 AWG) solid copper wire or
0.2…2.5 mm
2
(24…14 AWG) stranded copper wire
rated @ 90 °C (194 °F) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
Wire type Use copper conductors only
Terminal screw torque, max 0.6 Nm (4.4 lb-in)
(using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Input circuit type 120V AC 12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type Relay 24V DC sink
(standard and high-speed)
24V DC source
(standard and high-speed)
Event input interrupt support Yes, inputs 0…15 only
Power consumption, max 11 W – without plug-in modules
18.2 W – with plug-in modules
Power supply voltage range 20.4…26.4V DC Class 2
I/O rating Input:
120V AC, 16 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
24V DC, 1 A per point
(Surrounding air temperature 30 °C)
24 V DC, 0.3 A per point
(Surrounding air temperature 65 °C)
Insulation stripping length 7 mm (0.28 in.)
Enclosure type rating Meets IP20
Pilot duty rating C300, R150 —
Isolation voltage 250V (continuous),
Reinforced Insulation Type,
Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @
3250V DC I/O to Aux and
Network, Inputs to Outputs
250V (continuous),
Reinforced Insulation Type,
Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @
720V DC, Inputs to Aux and
Network, 3250V DC Outputs
to Aux and Network, Inputs
to Outputs
50V (continuous), Reinforced Insulation Type, I/O to Aux
and Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network,
Inputs to Outputs
North American temp code T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table of Contents

Other manuals for Allen-Bradley Micro830

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Micro830 and is the answer not in the manual?

Allen-Bradley Micro830 Specifications

General IconGeneral
BrandAllen-Bradley
ModelMicro830
CategoryController
LanguageEnglish

Related product manuals