Rockwell Automation Publication 2080-UM002K-EN-E - March 2019 73
Communication Connections Chapter 5
Configure CIP Serial Driver
1. Open your Connected Components Workbench project. On the device
configuration tree, go to the Controller properties. Click Serial port.
2. Select CIP Serial from the Driver field.
3. Specify a baud rate. Select a communication rate that all devices in your
system support. Configure all devices in the system for the same
communication rate. Default baud rate is set @ 38400 bps.
4. In most cases, parity and station address should be left at default settings.
5. Click Advanced Settings and set Advanced parameters.
OPC Support Using RSLinx
Enterprise
Support for Open Platform Communications (OPC) using CIP symbolic has
been added from firmware release 7.0 onwards. This can be used in place of
Modbus addressing.
RSLinx Enterprise version 5.70 (CPR9 SR7) or later and FactoryTalk Gateway
version 3.70 (CPR9 SR7) or later are required.